The race to build machines capable of training and running artificial intelligence models is turning cooling into a core part of the computer itself. NVIDIA’s most counterintuitive proposal is that its next-generation servers can receive coolant at up to 45°C—hotter than many hot tubs. The point is not to let the hardware run uncontrolled at high temperatures. It is to capture heat where it is produced, move it through a sealed loop, and change where the facility spends energy. NVIDIA presents the approach in its Rubin-generation infrastructure and the DSX AI factory reference design, which describes a system built around warm liquid rather than a chilled room.

The key is to stop trying to cool the entire space. In a conventional data center, mechanical systems chill air, fans push it through servers, and cooling towers may evaporate large amounts of water to reject the heat. NVIDIA’s approach sends coolant through a closed loop and directly into cold plates mounted on GPUs, CPUs, and other high-power components. The company’s DGX documentation describes the underlying arrangement: liquid travels through rack manifolds and across cold plates attached to the processors. Air is left for lower-power components, while Rubin’s full-system design is intended to cool every chip and networking component with liquid, without fans in the system.

How can liquid at 45°C cool anything? Because “cold” is relative to the chip, and the relevant question is whether the coolant is cool enough to absorb heat while keeping the silicon within its operating limits. NVIDIA says coolant enters a fully liquid-cooled processor at 45°C and leaves at roughly 55°C after collecting the chip’s heat load. The processor does not need near-freezing liquid; it needs a controlled thermal path that carries heat away continuously. Liquid also transfers heat far more effectively than air, avoiding the electricity required to chill and move huge volumes of air around increasingly dense racks. NVIDIA describes the coolant as a mixture of roughly 75% water and 25% propylene glycol, a formulation similar to antifreeze.

The warmer operating point unlocks the second half of the system. Because the loop is already hotter than outdoor air for much of the year, it can send heat to “dry coolers”—large radiator assemblies that exchange energy with the atmosphere without evaporating water. In suitable climates, this can eliminate mechanical chillers and evaporative cooling towers. NVIDIA estimates that its 45°C architecture could reduce facility cooling-water use from roughly 2.6 million gallons per megawatt per year to near zero, or by up to 100%. The company also cites an industry estimate that raising a cooling plant’s target temperature by 1°C can reduce cooling electricity use by about 4%. NVIDIA’s Vera Rubin technical overview connects the warm-water loop to heat exchangers and outdoor dry coolers.

That is also where the promise needs its qualifier. “Up to 100%” refers to water used by the facility’s cooling system under favorable conditions; it does not erase the electricity consumed by the GPUs, the water associated with generating that electricity, or the cost of retrofitting existing buildings. A heat wave that pushes outdoor temperatures beyond the system’s operating envelope may still require chillers, and liquid infrastructure introduces requirements for seals, leak detection, maintenance, and hydraulic design. NVIDIA’s materials also describe a reference architecture, not proof that every deployment will achieve the same savings. The advance is therefore not about making the heat disappear. It is about capturing it at the chip, circulating it in a closed loop, and rejecting it at a temperature that lets ordinary outdoor air do more of the work.